Heat Pump Using High Electricity in Summer – Hot Water Setup Issue
Heat Pump Using High Electricity in Summer – Hot Water Setup Issue
Heat Pump Using High Electricity in Summer – Hot Water Setup Issue
Heat Pump Using High Electricity in Summer – Hot Water Setup Issue
Heat Pump Using High Electricity in Summer – Hot Water Setup Issue

UK Heat pump Help Technical Team
Independent Heat Pump Engineer
System Type: Air Source Heat Pump (Domestic) LG
Issue Type: Hot Water Configuration / Running Costs
The Problem
A homeowner in North London contacted me after noticing unusually high electricity bills.
What stood out straight away was that the system was using a large amount of energy even during warmer weather, when heating demand should have been low.
What I Found
After reviewing the system setup and looking at monthly kWh usage, it became clear that the issue wasn’t with the heating — it was how the hot water system had been configured.
There were two key problems:
The hot water circulation pump had been left running 24 hours a day
The hot water was being heated using the immersion heater instead of the heat pump
The circulation pump constantly moves hot water around the system. If left on permanently, it causes continuous heat loss, meaning the system has to keep reheating water throughout the day.
On top of that, the immersion heater was doing the work instead of the heat pump — which is far more expensive to run.
What I Changed
Set up the hot water circulation to run on a timed schedule rather than continuously
Switched the system back so the heat pump heats the hot water instead of the immersion heater
Explained to the homeowner how and when to use the circulation system properly
The Outcome
The unnecessary energy usage was eliminated, and the homeowner saw a noticeable reduction in electricity consumption.
System Type: Air Source Heat Pump (Domestic) LG
Issue Type: Hot Water Configuration / Running Costs
The Problem
A homeowner in North London contacted me after noticing unusually high electricity bills.
What stood out straight away was that the system was using a large amount of energy even during warmer weather, when heating demand should have been low.
What I Found
After reviewing the system setup and looking at monthly kWh usage, it became clear that the issue wasn’t with the heating — it was how the hot water system had been configured.
There were two key problems:
The hot water circulation pump had been left running 24 hours a day
The hot water was being heated using the immersion heater instead of the heat pump
The circulation pump constantly moves hot water around the system. If left on permanently, it causes continuous heat loss, meaning the system has to keep reheating water throughout the day.
On top of that, the immersion heater was doing the work instead of the heat pump — which is far more expensive to run.
What I Changed
Set up the hot water circulation to run on a timed schedule rather than continuously
Switched the system back so the heat pump heats the hot water instead of the immersion heater
Explained to the homeowner how and when to use the circulation system properly
The Outcome
The unnecessary energy usage was eliminated, and the homeowner saw a noticeable reduction in electricity consumption.

Contact Us
Not Sure Which Service You Need?
Not Sure Which Service You Need?
Not Sure Which Service You Need?
Not Sure Which Service You Need?
Not Sure Which Service You Need?
Whether you need help with an existing heat pump, a pre-installation review, cooling advice, servicing or a room-by-room heat loss survey, send us a few details and we'll point you in the right direction.
Whether you need help with an existing heat pump, a pre-installation review, cooling advice, servicing or a room-by-room heat loss survey, send us a few details and we'll point you in the right direction.
Whether you need help with an existing heat pump, a pre-installation review, cooling advice, servicing or a room-by-room heat loss survey, send us a few details and we'll point you in the right direction.